单选题The outlet at a fire hydrant may be positioned anywhere from horizontal to pointing().A45°upwardBvertically upwardCvertically downwardDall of the above

单选题
The outlet at a fire hydrant may be positioned anywhere from horizontal to pointing().
A

45°upward

B

vertically upward

C

vertically downward

D

all of the above


参考解析

解析: 暂无解析

相关考题:

A fire hose with a nozzle attached must be connected to each hydrant except when exposed to heavy weather or when the ______.A.Fire hose might be damaged by cargo operationsB.Vessel is in portC.Fire-main system is not chargedD.Fire pumps are used for purposes other than supplying water to the fire main

The number and position of hydrants arranged on board shall be such that _______,one of which shall be from a single length of hose,may reach any part of the ship normally accessible to the passengers or crew while the ship is being navigated.A.at least two jets of water which shall be from the same length of hoseB.at least two jets of water emanating from the same hydrantC.at least two jets of water not emanating from the same hydrantD.at least two jets of water not emanating from the same hydrant,one of which shall be from a single length of hose

Which of the following statements is FALSE concerning the proper procedure in handling a fire hose ________.A.A 1.5 inch hose should be deployed with a minimum of a nozzleman and hosemanB.Back-up hosemen should be positioned wherever the hose makes a significant turnC.The fire hose should be partially charged before deploying it from the fire stationD.The nozzleman should always hold the nozzle with one hand on top,to prevent kickback

A galley grease fire on the stove may be extinguished using______.A.waterB.foamC.the range hood extinguishing systemD.fire dampers

If not attached to the nozzle, each low-velocity spray applicator on a vessel must be stowed__________.A.in a protected area on the main deckB.inside a machinery space near the entranceC.next to the fire hydrant to which the fire hose is attachedD.on a rack inside the quarters near the entrance

Which of the following best describes the lock protection provided by DB2 for the current row of a cursor?()A、The cursor is only protected from updates and deletes by concurrent applications.B、The row is only protected from positioned updates and deletes that reference another cursor of the same application.C、The cursor is protected from positioned updates and deletes that reference another cursor of a different application.D、The row is protected from updates and deletes by the current application and from positioned updates and deletes that reference another cursor of the same application.

单选题Which of the following statements is not true concerning symptom of a fire in the scavenge air box?()Aan increase in the exhaust temperature of the affected cylinderBthe turbocharger may surgeCthe explosion pressure in all cylinders will rise violentlyDsmoke from the turbocharger air inlet filter will be seen

单选题Which of the following best describes the lock protection provided by DB2 for the current row of a cursor?()AThe cursor is only protected from updates and deletes by concurrent applications.BThe row is only protected from positioned updates and deletes that reference another cursor of the same application.CThe cursor is protected from positioned updates and deletes that reference another cursor of a different application.DThe row is protected from updates and deletes by the current application and from positioned updates and deletes that reference another cursor of the same application.

单选题What is the most vulnerable part of the fire main system on board an offshore rig?()AThe fire pumpBExposed hard pipingCThe hydrant valveDThe fire hose

单选题A cutoff valve in the fire-main system of a ship may be closed to protect the portion of the system on an exposed deck from().Adamage from crane operationsBbeing used for wash down purposesCaccidental diversion of flow to wrong locationDfreezing

单选题Flames from small leaks of LFG may be extinguished by().Autilizing carbon dioxide or dry chemical fire extinguishersButilizing soda and acid fire extinguishersCblowing the flames outDletting it burn itself out

单选题In order to maintain a constant outlet water temperature of 80-85℃ from the engine, a three-way valve is installed()Aat the jacket cooler outlet to control the flux through the engineBat the jacket cooler outlet to control the flux through the coolerCat the engine outlet to control the flux through the engineDat the engine inlet to control the flux through the engine

单选题A high-velocity fog stream can be used in fire fighting situations to drive heat and smoke ahead of the fire fighters in a passageway. This technique should only be used when().Ausing a 2-1/2 inch hoseBthere is an outlet for the smoke and heatCthe fire is totally contained by the ship's structureDat least two fog streams can be used

单选题Which of the following conditions indicates the dilution of diesel engine lube oil by fuel oil?()AWater discharging from the water outlet of the lube oil purifierBFuel oil discharging from the water outlet of the lube oil purifierCLube oil discharging from the water outlet of the lube oil purifierDA change in the lube oil viscosity

单选题To remedy a leaking fire hose connection at the hydrant,secure the valve and().Areplace the gasket in the male couplingBreduce fire pump pressureCreplace the gasket in the female couplingDrethread the male coupling

单选题A fire hose has a().Amale coupling at both endsBfemale coupling at both endsCfemale coupling at the nozzle end and a male coupling at the hydrant endDmale coupling at the nozzle end and a female coupling at the hydrant end

单选题When joining the female coupling of the fire hose to the male outlet of the hydrant,you should make sure that the().Athreads are lubricatedBnozzle is attached to the hoseCfemale coupling has a gasketDhose is led out

单选题Each fireman’s outfit and its spare equipment on a ship must be stowed().Ain a locked cabinet in the machinery spaceBin an unlocked cabinet in the machinery spaceCin a separate and accessible locationDat a fire hydrant location

单选题Combustible material stored in a compartment adjacent to a compartment where there is a fire may be ignitedThis ignition can occur by ().Aheat convection through the adjacent bulkheadsBcombustion gases carried through the ventilation systemCdirect convection of the heat emitted by the adjacent fireDheat radiated from the dock or bulkhead by the adjacent fire

单选题Each fire hydrant serving machinery spaces containing oil fired boilers,internal combustion machinery,or oil fuel units must be equipped with a().Afireman's outfitBlow-velocity spray applicatorCmarine strainerDpick axe

单选题A fire hose with a nozzle attached must be connected to each hydrant except when exposed to heavy weather or when the().Afire hose might be damaged by cargo operationsBvessel is in portCfire-main system is not chargedDfire pumps are used for purposes other than supplying water to the fire main

单选题The system will include various () such as low tank level alarms and remote operation of tank outlet valves in the events of a fire.ASwitchesBpanelsCalarm unitsDsafety devices

单选题Each fireman’s outfit and its spare equipment on a tanker must be stowed in a(n)().Alocked cabinet in the machinery spaceBunlocked cabinet in the machinery spaceCseparate and accessible locationDlocation near a fire hydrant

单选题Each fire hydrant must have at least one spanner and at least one().Ahose rack or reelBall purpose nozzleCfoam applicatorDpick axe

单选题If not attached to the nozzle,each low-velocity spray applicator on a vessel must be stowed().Ain a protected area on the main deckBinside a machinery space near the entranceCnext to the fire hydrant to which the fire hose is attachedDon a rack inside the quarters near the entrance

单选题In a purifier, the interface between the liquid seal and the oil should be positioned as close as possible to ().Athe outlet of oilBthe outlet of waterCthe bowl peripheryDthe center of bowl

单选题No outlet on a fire hydrant may point above the horizontal in order to().Aavoid kinking the hoseBavoid personal injury during connectionCmake connecting easierDprevent spray on electrical equipment